Emergency Luminaire for Fluorescent Lamps EXLUX Series 6409/5
Art. No.:
255076
Product Type:
6409/522-9606-1611-7
min. ambient temperature:
-30 °C
Lamp wattage:
18 W
Number of lamps:
2
max. ambient temperature:
+50 °C
AC rated operational voltage:
110 - 127 V
Zone Filter:
Zone 2 | 3 G | Gc / Zone 21 | 2 D | Db / Zone 22 | 3 D | Dc
Product status:
-Emty-
Certificates:
ATEX (PTB), IECEx (PTB)
Lamp:
G13 lamp base
Luminous flux:
0 lm
Emergency light output:
100% – 1.5 h, 60% – 3.0 h
Enclosure material:
Polyester resin
Max. solid connection terminals:
6 mm²
Disconnection of the luminaire:
only battery
Through wiring:
with 6 conductors 2.5 mm2
Drilled holes:
3 x M25
Cable glands and entries:
2 x M25 Ø 7 … 17 mm
Country of origin:
DE
On request
Technical data
General
MY R. STAHL | 6409A |
Product Type | 6409/522-9606-1611-7 |
Highlights | Can be used in Zones 2, 21 and 22Weekly function test and annual emergency light duration test |
Functional Description | The 6409 Series EXLUX emergency luminaire is suitable for use as safety lighting. It is lightweight and requires minimal maintenance. The external battery powers the emergency lighting for 1.5 or 3 hours. If one lamp is faulty, the luminaire switches to the working lamp. When the luminaire or battery case is opened, the battery circuit is disconnected. The robust plastic enclosure of the luminaire is easy to open thanks to the practical central lock. |
Explosion Protection
Electrical Data
Lighting Data
Ambient Conditions
Mechanical Data
Components
Commercial data
Downloads
Description | Document Type | Language | |
---|---|---|---|
Emergency luminaire For fluorescent lamps GRP - 6409/522-9606-1611-7 - 255076 - de-DE | Single Data Sheet |
|
|
Emergency luminaire For fluorescent lamps GRP - 6409/522-9606-1611-7 - 255076 - en-GB | Single Data Sheet |
|
|
Emergency luminaire For fluorescent lamps GRP - 6409/522-9606-1611-7 - 255076 - fr-FR | Single Data Sheet |
|
|
Emergency Luminaire for Fluorescent Lamps EXLUX - 6409/5 - de-DE | Product Overview |
|
|
Emergency Luminaire for Fluorescent Lamps EXLUX - 6409/5 - en-GB | Product Overview |
|
|
Emergency luminaire For fluorescent lamps GRP - 6409/522-9606-1611-7 - 255076 - es-ES | Single Data Sheet |
|